24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

How is a clearance prepared on a medium-voltage line?

A clearance on a medium-voltage line is prepared by opening and isolating the line, locking it out, verifying the absence of voltage, grounding and short-circuiting it and marking off the zone, all under a document that transfers responsibility to a work supervisor.

What a clearance is and why it exists

A clearance is the procedure and the document by which a line or piece of equipment is declared out of service and handed over to a responsible person so that work can be done on it. It exists because opening a breaker is not enough: at medium voltage a line can remain energized from another source, by induction from neighboring lines, by backfeed from on-site generation or by stored charge. The clearance requires proving that the line is really free, not assuming it.

Logical sequence

  1. Identify the line and its sources. Using the single-line diagram and a field check, list every point through which energy can arrive: main supply, backup supplies, interconnections, transformers that can backfeed, and local generation.
  2. Request and authorize. The grid operator or the person responsible for the installation authorizes the switching. Nobody switches on their own initiative.
  3. Open the disconnection points. The line is interrupted at all sources, with devices capable of providing a visible or reliable break.
  4. Lock out and tag. Each disconnection point is locked with a personal padlock and tag so that it cannot be closed by mistake.
  5. Verify the absence of voltage. Use a detector suited to the voltage class, tested before and after the measurement, on each conductor.
  6. Ground and short-circuit. Grounding equipment is connected first to ground and then to the conductors, as close as possible to the work site and at the points from which voltage could arrive. This protects against accidental energization and against induced voltages.
  7. Mark off the zone. Physically mark which part is clear and which part remains energized, so that nobody confuses parallel circuits.
  8. Hand over the clearance. The person responsible for the switching hands over to the work supervisor, who confirms the scope verbally and in writing.

What is seen in practice

Problems rarely lie in the written procedure. They usually lie in an unidentified parallel circuit, a label that does not match the actual equipment, or an outdated diagram. That is why on-site verification carries more weight than any document.

Closing the clearance

The return follows the reverse order: the work supervisor confirms that personnel have withdrawn and that tools and materials have been collected, the grounds are removed, each person removes their own lockout with their own padlock, and only then is the line re-energized on the order of the responsible person.

Safety notice

This text describes the general logic. Switching and work at medium voltage must be done exclusively by qualified and authorized personnel, with the appropriate protective equipment and hot sticks, following the applicable regulations and the grid operator’s procedures.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer