Operation
A thermocouple consists of two conductors of different materials joined at one point, the measuring junction. At the other end, the conductors connect to an instrument. If the measuring junction and the ends at the instrument are at different temperatures, a small voltage appears, on the order of microvolts per degree, that depends on the pair of materials and the temperature difference. This is the Seebeck effect.
What it actually measures
A thermocouple measures a temperature difference, not an absolute temperature. To obtain the temperature at the measuring point, you need to know the temperature of the other end, the reference junction, and add it in the proper way. Hence the need for cold junction compensation.
Rules that make it practical
- Law of intermediate metals. If a third metal is inserted into the circuit, for example in connectors or solder joints, and its two ends are at the same temperature, the total voltage does not change.
- Law of intermediate temperatures. The voltage between two temperatures is the sum of the voltages of the intermediate intervals. This makes it possible to use tables referred to a single reference and to compensate.
Types and construction
There are several material combinations, designated by letters, that differ in range of use, sensitivity, resistance to oxidation and stability. Base metal thermocouples are economical and rugged; noble metal thermocouples are used at higher temperatures or where greater stability is needed. They can be built with the junction exposed, insulated from the sheath or grounded, with trade-offs among response speed, protection and electrical noise.
Advantages and limitations
| Advantages | Limitations |
|---|---|
| Wide temperature range | Lower accuracy than a resistance thermometer |
| Ruggedness and small size | Very small signal, sensitive to noise |
| Fast response with fine wire | Requires reference junction compensation |
| Low cost | Drifts with use at high temperature |
What the engineer sees
An old thermocouple that has worked at high temperature can change its response without giving any sign of failure. The reading still looks normal, but with an error that only a calibration or a comparison with another sensor reveals. That is why, in critical applications, thermocouples are compared periodically.
How to interpret the result
To expect a good result, the sensor must be homogeneous in the gradient zones, the cables must be of the proper type and the instrument must correctly compensate the reference junction.