The physical principle
A conductor carrying AC voltage creates a varying electric field around it. The detector has a high-impedance sensor that, as it approaches, couples capacitively to that field. The internal circuit amplifies the signal and, if it exceeds a threshold, lights an indicator or emits a sound. No voltage is measured: the presence of a varying field is detected.
Why it does not need metallic contact
Capacitive coupling works through the cable insulation. The circuit closes through the capacitance of the user’s body and of the surroundings to ground, which is why the detector can give an indication without touching the metal part.
What can give misleading results
- Shielding: cables with a metallic shield, metal conduit, cable trays or enclosures block the field and can cause voltage that is present to go undetected.
- Conductor with DC voltage: the principle requires a varying field, so direct current circuits are not detected in the same way.
- Conductor with ground alongside: if the conductor is close to others, the field can cancel out.
- Induced voltage or static charge: these can produce indications even if the circuit is de-energized.
- Low battery or degraded sensor: the instrument may become less sensitive or fail to respond.
- Position and orientation: sensitivity changes with angle and distance.
How to interpret the indication
A positive indication is a useful warning: assume that voltage is present. A negative indication does not prove that the circuit is de-energized. For this reason this instrument is considered a first supporting screen, not a sufficient means of confirming the absence of voltage before touching.
Correct use
- Test it on a known source before and after use.
- Bring it close slowly, trying several orientations.
- Follow up with a suitable contact tester to confirm absence.
Energized installations must be handled by qualified personnel following the applicable regulations.