How Does a Megohmmeter Work?

A megohmmeter generates a high DC voltage, applies it to the insulation under test, measures the tiny current that flows and displays the resistance obtained from Ohm's law.

The principle

An ordinary ohmmeter uses a voltage of a few volts, which is not enough to reveal defects in insulation designed to operate at hundreds or thousands of volts. A megohmmeter applies a much higher, selectable DC voltage and measures the resulting current. From that voltage and current, the instrument calculates the resistance and displays it on scales of megohms or higher.

What is inside

  • High-voltage DC source: a hand-cranked generator in older models; a battery-powered electronic converter in current ones.
  • Current meter: it must resolve very small currents, so the input circuits have very high impedance.
  • Line, ground and guard terminals: the guard diverts surface leakage currents so that they do not enter the measuring circuit.
  • Current limiting: protects the instrument and limits the energy if the insulation is defective.

Why the reading changes over time

The total current has three components: capacitive charging current, which disappears within seconds; dielectric absorption current, which decays more slowly; and conduction current, which remains constant. This is why the apparent resistance increases while the voltage is held. Comparing the reading at two different times gives the absorption or polarization index, which helps distinguish dry insulation from wet or contaminated insulation.

What a technician will see

On a motor in good condition, the reading rises and stabilizes. On a wet motor or one with conductive dirt, the reading is low from the start and hardly grows. A value that drops sharply during the test suggests a developing fault. Each reading is interpreted taking into account the temperature and the history of the same equipment.

Common errors

  • Measuring without de-energizing the equipment or disconnecting it from other circuits.
  • Choosing a test voltage that is excessive for the insulation, which can damage it.
  • Not using the guard when there is significant surface leakage.
  • Touching the test leads or the equipment as soon as the measurement ends, without discharging the stored capacitance.
  • Test leads in poor condition or dirty, which add leakage.
  • Comparing values measured at different temperatures.

Because of the voltages involved, use of the instrument on power equipment is reserved for qualified personnel who follow the applicable regulations.