How Does a Circuit Breaker Electronic Trip Unit Work?

An electronic trip unit measures current with sensors, calculates its RMS value in a microprocessor and commands the breaker to open according to configurable protection curves for overload, short circuit and ground fault.

How it detects current

Each phase has a current sensor, such as a current transformer or a Rogowski coil, built into the breaker. The signal is conditioned and sampled, and a microprocessor calculates the RMS value. The electronics are powered by the line current itself, and often by an auxiliary source for displays and communication. Once the decision is made, a low-energy actuator releases the breaker mechanism so that it opens.

Protection functions

The usual nomenclature uses letters for each zone of the curve:

  • L (long delay): protects against overloads. Its trip time is inverse: more current, less time. It supports thermal memory, which remembers recent heating.
  • S (short delay): acts on high currents with an adjustable delay, to allow selectivity with downstream breakers.
  • I (instantaneous): trips without delay on short-circuit currents.
  • G (ground fault): detects current to ground, either by summing the phase and neutral currents or by measuring the current in the ground conductor.

What is adjusted

The current level of each zone and its time are adjusted. Some units include a maintenance mode to temporarily reduce the trip time and the arc energy, as well as imbalance protection, energy metering and communications. The settings must come from the coordination study.

Difference from thermal-magnetic protection

A thermal-magnetic trip uses a bimetal that deforms with heat and an electromagnet, so its curves depend on ambient temperature and are barely adjustable. The electronic unit is more accurate, repeatable and flexible, at the cost of depending on the electronics and their power supply.

What the engineer sees

Trip type indicators, which help distinguish an overload from a short circuit or a ground fault, and an event log. Units are tested with the manufacturer’s test equipment or by current injection. Work is done with the breaker out of service, by qualified personnel in accordance with applicable regulations.