The idea
An oil can dissolve water up to a limit, the saturation solubility. That limit is not fixed: it grows with temperature and depends on the type and aging condition of the oil. The concentration measured in parts per million does not by itself say whether the oil is dry or saturated. Relative saturation does, because it normalizes the measurement against the limit.
The calculation
- Measure the water content of the oil, for example with a Karl Fischer method, in units of mass of water per mass of oil.
- Record the temperature of the oil at the time of sampling, not that of the laboratory.
- Obtain the saturation solubility at that temperature for that type of oil. It is calculated with an empirical relationship in which the logarithm of the solubility varies approximately linearly with the inverse of the absolute temperature, using constants specific to each oil provided in the literature or by the manufacturer.
- Divide the water content by the solubility and multiply by one hundred.
A result close to zero percent corresponds to a very dry oil; a value close to one hundred percent means the oil is saturated and any additional water separates out as free water.
Why it is useful
Relative saturation is related to the moisture of the paper at equilibrium: paper in equilibrium with a given oil has a water content that depends mainly on relative saturation and less on temperature. That makes it a better indicator of the moisture of the solid insulation than the concentration in parts per million. It is also related to dielectric strength, which falls as saturation approaches.
Precautions
- Solubility constants are specific to each type of oil; using those of another introduces a systematic error.
- A temperature error is amplified, because solubility changes rapidly with temperature.
- Equilibrium with the paper may not have been reached, so the result is an estimate.
- Aged oils, with more polar compounds, can dissolve more water.
How to interpret the result
A low percentage indicates that the solid insulation is probably dry. A high value signals a risk of loss of strength and of water being released on cooling, and calls for corrective action and follow-up.