Oil moisture test
The oil moisture test measures the water content of insulating oils, such as those in transformers and other electrical equipment. Moisture is a critical factor: water lowers the insulating capacity of the oil and increases the risk of equipment failure.
Importance of the test
Insulating oil performs several functions, including insulating conductive parts, dissipating heat and protecting against corrosion. When it becomes contaminated with water, its ability to insulate decreases. This can increase conductivity, form acids that accelerate oil degradation and corrode the metal parts of the equipment.
Knowing the amount of water in the oil makes it possible to evaluate its quality and decide whether it needs to be purified or replaced. The test is also key to predicting the service life of the oil and, with it, that of the transformer or electrical equipment.
Karl Fischer (KF) method
This is one of the most widely used and reliable methods for measuring moisture in insulating oils. It is based on the Karl Fischer chemical reaction, which determines with high precision the amount of water in an oil sample.
Process
- A solution of reagents is prepared in a suitable medium, usually an alcoholic solution containing iodine and sulfur.
- The water in the sample reacts with these reagents and releases iodine.
- The released iodine is titrated with a standard solution; the volume of reagent used correlates with the amount of water in the sample.
Advantages
- High precision.
- A very specific method for measuring water content, even at very low concentrations.
