Two sides that can stop the session
Charging is started and ended by an agreement between two pieces of equipment. It can be stopped by the station, the vehicle or an external event, and the first diagnostic question is which of the two did it.
Causes on the station side
- Residual current protection: a ground leakage current trips it. Many stations also detect DC leakage, which a standard residual current device would not see.
- Overtemperature: a connector, cable or internal electronics heating up first causes a power reduction and then a stop.
- Loss of ground or pilot faults: the station detects an unsafe condition and opens the contactor.
- Contactor with welded contacts or wear: the station detects it and locks out.
- Metering or authorization: loss of connection with the management system, or expiry of the authorization time.
Causes on the vehicle side
The battery management system can ask to stop or reduce current because of cell temperature, maximum voltage, state of charge reached or an internal fault. The on-board charger can stop because of overtemperature or an insulation problem. And the vehicle can cut off charging if it loses the proximity signal or if the connector unlocks.
Grid causes
A voltage out of range, a voltage sag or an interruption makes the station suspend the session. An overloaded installation with voltage drops also causes it.
How to diagnose it
- Review the station’s event log and the vehicle’s code log.
- See whether the cutoff occurs at a similar moment: after minutes at maximum power, it points to heat; at the start, to communication.
- Test with another vehicle or with a simulator, to separate the origin.
- Measure the voltage and power quality of the supply during the session.
Physical checks of energized stations must be carried out by qualified persons, in accordance with the applicable regulations.