What is potential-induced degradation?

Potential-induced degradation (PID) is a loss of module power caused by the voltage difference between the cells and the grounded frame, which promotes leakage currents and the migration of ions toward the cells, especially in the presence of humidity and heat.

What happens physically

In a high-voltage string, the cells at one end sit at a high voltage relative to the frame, which is grounded. That electric field, combined with humidity and temperature, drives leakage currents and the movement of ions, such as sodium, through the glass and encapsulant toward the cell. The ions alter the junction and reduce the shunt resistance of the affected cells.

What conditions favor it

  • Higher system voltage and the position of the cell within the string, with those closest to the negative or positive pole more exposed depending on the cell type.
  • High humidity and temperature, which increase the conductivity of surfaces and materials.
  • Glass and encapsulant materials that are more permissive to the passage of ions.
  • The type of cell and anti-reflective coating, which determine susceptibility.

How it shows up

Power falls gradually and unevenly: the modules at one end of the string lose more than those at the other. The I-V curve shows a lower fill factor and a steeper slope near short circuit, characteristic of low shunt resistance. Electroluminescence shows dark or extinguished cells in a systematic pattern. In thermography, some cells appear hotter.

Reversibility and mitigation

In certain cases the effect is partially reversible and is corrected by applying a reverse voltage or through nighttime recovery. Mitigation includes choosing modules that have demonstrated resistance to PID in tests, adjusting the system grounding type, limiting the string voltage and, where appropriate, using recovery equipment.

How to distinguish it from other causes

A loss pattern that correlates with electrical position in the string points to PID. Soiling or shading acts according to physical location, not electrical position. That difference guides the diagnosis before any corrective measure is planned.

Notice

Any work on an energized photovoltaic array, with DC voltages that are not interrupted by opening a disconnect switch on the AC side, must be carried out by qualified personnel in accordance with the applicable electrical safety regulations.