What is being looked for
The insulation between the live conductors and ground must be high. If it falls, there is a leakage path to ground through moisture, mechanical damage, aged insulation, deteriorated connectors or defective modules. That leakage can cause trips of the inverter’s insulation monitoring, corrosion and, in the worst case, a risk of shock or fire. Insulation measurement is a commissioning and maintenance test.
Measurement principle
An insulation tester applies a DC test voltage and measures the resulting leakage current, from which it calculates the resistance. The test voltage is chosen according to the system voltage and the instructions of the regulations and the manufacturer; it must not exceed what the connected equipment can withstand.
What is particular about a PV array
An array cannot be “switched off”: it generates voltage as long as there is light. That is why the procedure is special. The positive and negative conductors of the array are short-circuited to each other in a controlled way, with suitable devices, to measure between the joined conductors and ground, so that the test does not depend on the generated voltage. The array is also disconnected from the inverter and from protection devices sensitive to the test voltage.
General steps
- Follow the approved procedure and disconnect the array from the inverter.
- Verify the absence of unintended ground connections and disconnect sensitive surge protection devices, according to the instructions.
- Connect the tester between the set of live conductors and the ground or the frame.
- Apply the test voltage for the specified time and read the stabilized resistance.
- Discharge the circuit before handling it, because capacitance retains charge.
How to interpret the result
The acceptance criterion is taken from the applicable standard and the manufacturer. A low reading is located by dividing the array into sections and repeating the test until the leaking string or module is isolated. Humidity conditions affect the value: it is advisable to record the weather. If the result changes with rain, it points to water ingress.
The test involves dangerous voltage: it must be carried out only by qualified, authorized personnel, following the applicable safety regulations.