Catalytic or infrared sensor for combustible gases?

A catalytic sensor detects combustibles by burning them on a hot element and needs oxygen; an infrared sensor measures light absorption by hydrocarbons, does not depend on oxygen and is not poisoned, but it does not detect hydrogen. Each suits different gases and conditions.

Two different principles

A catalytic sensor measures the heat produced by oxidizing the gas on a heated bead. An infrared sensor sends infrared light through the sample and measures how much is absorbed at the wavelengths characteristic of the gas’s bonds. The first detects a chemical reaction; the second detects an optical property of the molecule.

Comparison

Aspect Catalytic Infrared
Needs oxygen Yes No
Works in an inert atmosphere Not reliably Yes
Poisoning Vulnerable to silicones, sulfur and halogenated compounds Not poisoned in that way
Hydrogen Detects it Does not detect it
Hydrocarbons Detects them, with variable response Detects them with good selectivity
Self-diagnostics Limited; requires a gas test Many models detect their own faults
Cost Generally lower Generally higher

The differences that settle the choice

Hydrogen

A molecule made up of two identical atoms does not absorb usefully in the infrared. That is why an infrared sensor is no use if the gas of interest is hydrogen. In that case a catalytic sensor or another technology is used.

Oxygen-poor atmospheres

In inerted or low-oxygen tanks, a catalytic sensor underestimates or fails to detect. An infrared sensor keeps measuring, so it is the option when the atmosphere does not contain enough oxygen.

Contaminating environments

Where compounds that damage the catalyst are present, an infrared sensor retains its sensitivity with no silent deterioration.

Fail-safe behavior

A poisoned catalytic sensor can keep showing zero. Many infrared sensors warn of an obstruction or optical fault.

How to decide

  1. Identify the combustible gas or gases expected.
  2. If they include hydrogen, the catalytic sensor is the practical option.
  3. If oxygen may be low or there is a risk of poisoning, prefer infrared.
  4. Consider maintenance, cost and the availability of calibration gas.

With either type, calibration is done with a reference gas and correction factors are applied. Selection and use must be handled by trained people, in accordance with current regulations.

This guide is for information only. Work involving electrical hazards, heights or hazardous atmospheres must be carried out by qualified, authorized personnel, following the applicable regulations.