What happens in the rotor
In a squirrel-cage rotor, the bars carry currents induced by the rotating field of the stator. If a bar breaks or loses contact with the end ring, it stops conducting, and the neighboring bars carry a higher current. The rotor field is no longer symmetrical, and an asymmetry appears that rotates with the rotor.
How it shows up
- In the current: sidebands around the line frequency, spaced at twice the slip multiplied by the line frequency. This is the classic indicator in motor current analysis.
- In the vibration: sidebands appear around running speed, spaced at the pole pass frequency, along with greater amplitude modulation.
- In operation: current and speed pulsations, and increased heating, especially at high load.
Why slip is used
The rotor asymmetry rotates at slip speed relative to the stator field. That is why the fault signal is modulated at that frequency, which is small, and resolving it requires a spectrum with good frequency resolution and a measurement with the motor under stable load. At light load the slip is minimal and the sidebands merge with the main component.
How it is confirmed
- Measure at the highest and most stable load possible.
- Use high-resolution spectra.
- Compare current and vibration, since they reinforce each other.
- Rule out other causes of modulation, such as misalignment, looseness or a pulsating load.
Measurements on energized motors must be made by qualified personnel and in accordance with the applicable electrical safety regulations.