Why it is treated with caution
Polychlorinated biphenyls are very stable chlorinated organic compounds that persist in the environment and accumulate in living organisms. They were used as insulating fluids because of their stability and fire resistance, and today they are subject to strict regulation. Their incomplete combustion can form even more toxic compounds, such as dioxins and furans, so they cannot be incinerated in the ordinary way.
How PCBs end up in equipment
- Old transformers originally filled with fluids that contained them.
- Cross-contamination: mineral oil that passed through hoses, pumps, tanks, or equipment that previously handled PCBs.
- Accidental mixing during equipment reconditioning.
How they are detected
The nameplate is not enough. The determination is made in the laboratory, using gas chromatography techniques that measure the concentration. There are also rapid field tests that serve for screening, but a positive or doubtful result is confirmed by the laboratory method.
Handling principles
- Identify before handling: treat equipment of uncertain origin as potentially contaminated.
- Segregate and label the equipment and containers; do not mix with other oils, because a mixture contaminates the entire volume.
- Prevent leaks with secondary containment and periodic monitoring.
- Protect personnel with suitable equipment, avoiding skin contact and inhalation.
- Manage through authorized channels: storage, transport, and destruction by permitted companies and procedures.
- Document inventory, analyses, and movements.
The concentration thresholds that define each category are set by regulation; consult the regulations in force. All work on electrical equipment must be done by qualified personnel, following the applicable regulations.