What degassing does and does not do
Vacuum treatment removes dissolved gases from the oil and, depending on the equipment and the procedure, part of the water. It does not repair the cause that generated them. If a fault is still active, the gases return, and degassing will only have erased the evidence that made diagnosis possible.
Factors weighed in the decision
- Origin of the gases: active fault, fault already corrected, residual air after filling, or gassing without a fault?
- Proximity to saturation: gas-laden oil can release gas as bubbles with changes in temperature or pressure.
- Moisture: wet oil and paper reduce the dielectric margin and promote aging; drying the insulation goes deeper than drying the oil.
- Historical trend: if the gases are stable and not evolving, the reason for degassing is mainly preventive.
- Type of equipment: in units with a gas blanket or online monitoring systems, degassing alters the reference.
What an engineer sees in practice
The usual order is: diagnose, correct the cause if there is one, degas, and re-establish a baseline with subsequent sampling. Then monitor whether the gases reappear. If they reappear quickly, the fault was not resolved.
When it does not apply
- While an undiagnosed active fault exists: investigate first.
- If the only goal is to “improve” a number in a report without understanding its origin.
- When the real problem is moisture in the paper, which oil treatment does not solve on its own.
Before treating the oil, keep samples and results to preserve the history. The process on energized equipment or with a vacuum in the tank must be in the hands of qualified personnel, in accordance with the manufacturer’s instructions and the applicable regulations.