Where bubbles originate
A bubble is gas or vapor leaving a phase in which it was held. In a transformer there are three main sources, and all are activated by temperature.
Dissolved gas being released
Oil dissolves air and other gases. Solubility changes with temperature and pressure; if the oil is close to saturation and is heated or depressurized, the gas comes out of solution. Oil that was poorly degassed after filling is a typical candidate.
Moisture in the paper
Insulating paper and pressboard retain water. When an area becomes very hot, the water leaves the cellulose quickly and can form vapor or bubbles. This effect is more likely the wetter the insulation and the hotter the critical point of the winding.
Gas produced by a fault
A hot spot or a discharge decomposes the oil and cellulose, generating combustible gases at the very site of the fault.
Why they matter
- Gas has lower dielectric strength than oil, so a bubble in a high-field zone can undergo discharges.
- Discharges decompose more oil and generate more gas, a worsening cycle.
- Bubbles can accumulate in the gas relay and cause alarms or trips.
What an engineer sees in practice
Gas relay alarms after load peaks, dissolved gases that increase with temperature, and high water content in the oil. To separate the causes, the composition of the trapped gas and of the dissolved gas is analyzed: if it is air, this points to a degassing or sealing problem; if it contains combustible gases, to a fault.
When this does not apply
Apparent foam when taking a sample or filling is not evidence of bubbles in service: it may be due to handling. Any intervention on energized equipment must be carried out by qualified personnel following the applicable regulations.