Color as a symptom
New mineral oil is clear, with a pale amber tone. With operation, it becomes darker. A color change is not a diagnosis in itself, but a sign that something is happening in the oil, and it can have several causes.
Main causes
- Oxidation: dissolved oxygen, heat, and catalytic metals such as copper react with the oil and produce acids and, over time, sludge. These products darken the liquid.
- Sustained overheating: accelerates oxidation and also degrades the solid cellulose insulation, whose products pass into the oil.
- Internal arcing or discharges: can form carbon particles that blacken the oil quickly and also generate characteristic dissolved gases.
- Contamination: manufacturing residues, gasket material, varnishes, or oil mixed with another of different composition.
- Moisture and particles: promote degradation and cloud the liquid.
What a technician sees in a sample
A slightly darkened sample with an acidic or sour smell points to aging. A black sample with visible particles means an active fault must be ruled out. Color alone does not distinguish between the two situations, which is why color is complemented by other tests.
Analyses that help
- Neutralization number or acidity: indicates how far oxidation has progressed.
- Interfacial tension: falls as polar degradation products accumulate.
- Dissolved gas analysis: gives guidance on overheating or discharges.
- Water content and dielectric strength: assess moisture and insulating capability.
- Particle and furan content: suggest contamination and cellulose degradation.
What to do with the result
Depending on the diagnosis, you can continue monitoring more frequently, reclaim or filter the oil, or investigate an internal fault. Changing the oil without addressing the cause only resets the clock.
Common mistakes
- Deciding by visual appearance without tests.
- Taking samples without following the procedure, with dirty containers or containers exposed to air.
- Mixing oils without verifying their compatibility.
- Being alarmed by slight darkening in old equipment with stable results, or ignoring rapid darkening.
Sampling on energized equipment must be done by qualified personnel, following the applicable safety regulations.