How does an online gas monitor work?

An online gas monitor is installed on the transformer, continuously extracts gases from the oil through a membrane or a chamber, and measures them with sensors or a compact chromatograph to record how they evolve and raise an alert if they increase.

What it does

Instead of waiting for a periodic sample, the monitor measures the concentration of one or several dissolved gases continuously or at short intervals and sends it to the supervision system. The advantage is detecting in time a fault that develops quickly between two samplings.

How it works

Extraction

The monitor connects to a tank valve. A gas-permeable membrane, or a chamber in equilibrium with the oil, separates the dissolved gases and carries them to the sensor without letting the liquid through.

Detection

  • Hydrogen sensors (or hydrogen and carbon monoxide sensors), which are the simplest and least expensive.
  • Multi-gas monitors with detection by thermal conductivity, infrared or photoacoustic spectroscopy, or a miniature chromatograph.

Some units include an oil moisture sensor.

What an engineer sees in practice

Trend plots for each gas, with alarms by level and, above all, by rate of increase. A sudden jump in hydrogen or acetylene triggers immediate action. The data make it possible to correlate gases with load and temperature.

Limitations

  • Single-gas monitors do not identify the type of fault.
  • Sensors drift over time and require verification and calibration.
  • Accuracy is usually lower than that of laboratory analysis.
  • Gases change naturally with oil temperature, which calls for careful interpretation.

How it is used in practice

A monitor alarm is confirmed with a sample analyzed in the laboratory, which provides the complete gas profile for diagnosis. Installing or connecting it to energized equipment must be done by qualified personnel, following the applicable safety regulations.