Furans in oil, such as 2-furfural, are measured by extracting them from the oil and analyzing them by liquid chromatography with an ultraviolet detector; their presence reflects thermal degradation of the cellulose in the insulation.

Where they come from

Insulating paper and pressboard are made of cellulose. When cellulose degrades through heat, moisture, or oxygen, its chain breaks and furan-derived compounds form and pass into the oil. The best known is 2-furfural. Measuring them gives indirect information about the condition of the solid insulation, which cannot be sampled without opening the equipment.

How it is measured

  1. An oil sample is taken with the same precautions as for other analyses, protected from light and contamination.
  2. The furans are extracted from the oil, for example with a polar solvent or by solid-phase extraction.
  3. The extract is injected into a liquid chromatograph, where the different compounds are separated.
  4. An ultraviolet absorption detector responds to each furan, which is quantified with calibration curves prepared from standards.

The result is reported as the concentration of each compound, in milligrams per liter or parts per billion.

What they indicate

A growing presence suggests ongoing degradation of the cellulose. There are empirical correlations between furan concentration and the degree of polymerization of the paper, a measure of its mechanical strength, but they are approximate.

What limits interpretation

  • There is no way of knowing where in the equipment the degradation originated; a local hot spot and general aging can give similar values.
  • The type of paper (thermally upgraded, for example) changes the production of each compound.
  • Furans are lost or reduced when the oil is reclaimed, replaced, or treated, which breaks the trend.
  • Temperature conditions influence the partitioning between paper and oil.

How to use it

Interpret it through the trend, together with CO and CO2 in dissolved gases and with the loading history. It is an indication, not a direct measure of remaining life.