Why it is measured
Particles of fiber, metal, carbon, or dust reduce the dielectric strength of the oil, especially when combined with moisture, and can indicate pump wear, shedding of cellulose, or contamination during filling. In equipment with forced circulation, they also damage the pump bearings.
Automatic particle counter
The sample flows through an illuminated cell. Each passing particle blocks part of the light, and the detector generates a pulse whose height depends on the projected area. By comparing the pulses with the instrument calibration, each particle is assigned to a size range. The result is the number of particles per unit volume in each range, sometimes expressed as a cleanliness code.
Counting by filtration
A volume of oil is passed through a membrane, the residual oil is washed out with solvent, and the membrane is examined under a microscope or weighed to obtain the mass of contaminant. This shows the shape and nature of the particles, something the optical counter cannot distinguish.
Sample preparation
- Shake or homogenize to resuspend settled particles.
- Degas or let stand to remove bubbles, which the counter counts as particles.
- Take note of free water, which is also counted as particles.
- Use clean materials and rooms or hoods with low ambient contamination.
What an engineer sees in practice
A very high result after filling indicates insufficient filtration. An increase in service may point to mechanical wear or paper degradation. Results are compared with the cleanliness criteria set for that type of equipment.
How to interpret the result
Combine the count with dielectric strength, water content and, where appropriate, an analysis of the particle type before deciding whether the oil needs to be filtered again.