How Is Aged Oil Regenerated?

Aged oil is regenerated by passing it through an adsorbent medium, such as Fuller's earth or activated alumina, that retains acids and polar compounds; it is then re-inhibited to restore its protection against oxidation.

What regeneration is

Regenerating, or reclaiming, an oil means removing the oxidation products it contains to restore properties close to those of new oil. Unlike filtering, which removes particles and water, regeneration removes dissolved contaminants, especially polar ones.

How it works

The oil, at a controlled temperature, is passed through columns of a high-surface-area adsorbent, for example Fuller’s earth or activated alumina. Polar compounds (acids, peroxides, sludge precursors) adhere to the surface of the medium, while the base oil molecules pass through. A filtration and degassing stage removes particles, adsorbent fines, water and gases. At the end, oxidation inhibitor is usually added again, because the process removes or reduces it.

What is recovered

  • Acidity decreases.
  • Interfacial tension rises.
  • Color lightens.
  • Oxidation stability and dielectric losses improve.

What it does not correct

It does not repair paper that has already degraded; aged solid insulation remains aged. Nor does it reliably remove sludge already deposited on windings and ducts, which requires physical cleaning or flushing. And it does not solve a mechanical or electrical problem in the equipment that caused the deterioration.

How to verify it

Analyses before and after are compared: acidity, interfacial tension, color, inhibitor content, dielectric strength, water and particles, and follow-up continues over the following months. The spent adsorbent is a waste that is handled according to environmental regulations.

Safety

The treatment involves hot oil and connections to the transformer; it must be carried out by qualified personnel, with the equipment under the corresponding safety conditions.