What Is the Interfacial Tension of Oil?

Interfacial tension is the force of attraction at the contact surface between oil and water; it falls when the oil accumulates polar oxidation compounds, which makes it an early indicator of aging.

What it is

At the surface separating two immiscible liquids, such as oil and water, the molecules attract one another in such a way that the interface behaves like a taut membrane. That force per unit length is the interfacial tension, and it is expressed in millinewtons per meter. A clean, refined oil forms a very well-defined interface with water and has a high value.

Why it falls

Oxidation products, acids, peroxides and other polar substances have an affinity for water. They accumulate at the interface and reduce the tension. Contaminants that dissolve in the oil, such as residues of internal varnishes, resins or paints, and incompatible manufacturing materials also reduce it.

What an engineer sees in practice

It is a very sensitive indicator: interfacial tension falls before acidity rises noticeably, so it gives early warning of aging. A new oil gives a high value; over the years it declines, and when it reaches low levels there is usually sludge in solution about to precipitate. That is why it is used together with acidity to decide when to regenerate the oil.

How it is measured

Oil is placed over distilled water in a vessel at a defined temperature, and the force needed to pull a platinum ring away from the interface is measured (ring method), or the drop technique is used. Details such as ring cleanliness, contact time and water purity influence the result.

How to interpret the result

  • A gradual drop is expected aging.
  • A sharp drop after filling or repair suggests contamination with some material.
  • Low values with low acidity point to contaminants other than oxidation.

Decision limits are taken from the current standard for maintenance of in-service oil.