What it is
New mineral oil is practically neutral. Over time, oxygen, heat and the metals present (especially copper) oxidize some of its hydrocarbons and form organic acids, peroxides and other polar compounds. Acidity is the amount of these acidic compounds and is expressed as the mass of potassium hydroxide needed to neutralize one gram of oil.
What it causes in the equipment
- Acids attack the cellulose of the solid insulation and accelerate its loss of mechanical strength.
- They corrode metal surfaces and form metallic soaps.
- They are precursors of sludge, which deposits on windings and cooling ducts and hinders heat dissipation.
- They increase the conductivity and dielectric losses of the oil.
What an engineer sees in practice
The value is compared with that of the initial delivery and with previous samples. What matters is the slope: a gradual increase is normal aging, while a sudden jump suggests overheating, contamination or inhibitor depletion. Acidity is rarely interpreted alone; it is compared with interfacial tension, color and sludge content, because they all reflect the same process from different angles.
How it is obtained
It is determined by titrating a portion of oil dissolved in a solvent mixture with a standard alkaline solution, detecting the end point by color indicator or by potentiometry.
How to act
If the trend is rising, the sampling interval is shortened, the inhibitor is checked and oil regeneration is evaluated before deposited sludge forms, because once it adheres to the winding it can no longer be removed just by treating the liquid. Acceptance criteria are set by the standards for maintenance of in-service oil.