Definition
Breakdown voltage is the voltage value at which dielectric failure of a material or an insulating gap occurs: a conductive channel forms and the current rises sharply. It is a test result for a specific sample, not an intrinsic property of the material.
Difference from dielectric strength
Dielectric strength is the breakdown voltage expressed per unit of thickness, that is, an electric field. It is a good approximation only when the field is reasonably uniform. With pointed electrodes or sharp edges the field concentrates, and breakdown occurs at a much lower voltage than dividing by the thickness would suggest.
What it depends on
- Thickness and electrode geometry: these define the field distribution.
- Waveform and rate of rise: AC, DC and impulse give different results; a faster ramp usually yields higher values.
- Moisture, contamination and particles: these reduce the value, especially in liquids and porous materials.
- Temperature and aging.
- Internal defects: voids, bubbles or inclusions that produce partial discharges.
What an engineer sees in practice
Results show scatter: several tests of the same material do not give the same number, so several determinations are averaged and the variation is reviewed. Breakdown in solids is destructive and leaves a carbonized or punctured channel; in liquids and gases it is recoverable, although it can leave byproducts.
How to interpret the result
A low value in an oil or insulator usually points to moisture or contamination rather than a failure of the base material. A high value does not guarantee a long service life, because aging from partial discharges occurs well below the breakdown voltage. Compare only results obtained with the same method, electrodes and conditions.
Breakdown tests use high voltage and must be performed by qualified personnel, under the applicable safety regulations.