24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

What causes carbonization of an insulator surface?

Surface carbonization of an insulator is caused by the localized heat of small discharges or arcs on the surface, which decomposes the organic polymer and leaves carbon, a conductive residue that facilitates further discharges.

The central mechanism

Polymers are compounds of carbon and hydrogen. When a discharge or a hot spot supplies enough energy, the chains break and the volatile components are given off. What remains may be carbon, which, unlike the original polymer, conducts electricity. Once formed, the carbon concentrates the field at its ends and promotes more discharges: the process feeds itself.

Most frequent origins

  • Tracking: leakage currents across a contaminated, wet surface which, as the film dries unevenly, produce discharges. It leaves branched lines of carbon, often tree-like in appearance.
  • Partial discharges or surface corona: at edges and corners with an intense field, which erode and blacken the area.
  • Arcs from switching or faults: intense, localized carbonization, with melting or spattering of material.
  • Overheating: a loose contact or a high-resistance connection heats the insulator until it decomposes. Here the origin is thermal and not necessarily a discharge.

How to tell them apart

The shape of the damage provides information. Fine, branched paths between electrodes suggest tracking. A broad stain centered on one point, with discoloration fading outward, points to heat. Pinpoint marks with spattered or melted material suggest an arc. The location relative to conductors, edges and contamination zones completes the diagnosis.

What makes it worse

  • Creepage distances insufficient for the level of contamination.
  • Materials with a low tracking index, especially if they carbonize easily.
  • Humidity, condensation and conductive dust.
  • Connections without proper tightening.

What to do with the evidence

Before cleaning, photograph and document the shape of the damage. A carbonized material does not recover: the surface must be replaced or reinsulated, and the cause must be corrected. Reviewing the design in terms of distances, shape and material is part of the solution.

Safety

If the element is part of an energized installation, inspection and repair must be carried out by qualified personnel, following the applicable regulations.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer