What it is for
It is used to check that insulation withstands a voltage higher than the working voltage without puncturing, or to determine the voltage at which a sample fails. These are two different uses: verifying that a level is exceeded, or taking the sample to failure to measure breakdown.
Main parts
- High-voltage source: a step-up transformer in the AC version, or a multiplier or converter for DC.
- Ramp control: raises the voltage in a controlled way, at an adjustable rate.
- Voltage measurement: by means of a divider or from the transformer ratio.
- Current detection: a trip threshold that cuts the output when the current exceeds a set value.
- Energy limiting: a series impedance or a circuit that limits the short-circuit current.
Normal leakage current versus breakdown
All insulation has capacitance, and under AC voltage a capacitive current flows that grows with the voltage and with the size of the object. This is not a failure. The trip threshold must be set above that current, or the instrument will trip with no breakdown present. With DC, the capacitive current appears only during charging, leaving the resistive leakage, which is what reveals the condition of the insulation.
AC or DC
AC voltage subjects the insulation to a stress similar to that in service. DC requires less source power for highly capacitive objects such as long cables, but the field distribution is different and the results are not equivalent to each other.
What the engineer sees
On failure, there is a jump in current, the instrument trips and, in a sample, a hole or carbonization is seen. If the instrument trips earlier than expected, check the load capacitance, surface moisture, edge discharges and the threshold setting.
Safety
High voltage and stored energy are dangerous. This equipment must be operated only by qualified personnel, with the object discharged after the test and with barriers and interlocks, in accordance with the applicable regulations.