General scope
IEC 61000-4-5 is a basic standard in the IEC 61000 series that establishes the method for evaluating the immunity of equipment to high-energy surges, such as those arising from switching on the grid and from the indirect effects of lightning. It describes the test and the characteristics of the generator, and leaves the choice of levels and criteria to the product standards.
What it describes
- Generator: a combination waveform, which produces an open-circuit voltage pulse and a short-circuit current pulse, with a defined source impedance.
- Coupling/decoupling networks: injection of the pulse into the power lines without it propagating to the mains, and specific networks for communication lines.
- Application modes: between conductors (line to line) and between conductors and ground (line to ground), with different coupling elements.
- Application: number of pulses, polarities and relationship to the phase of the mains voltage where applicable.
- Evaluation: performance criteria during and after the test.
What sets it apart
Unlike fast bursts, a surge involves much more energy in each pulse, and failures can be destructive: protective devices that operate, degraded varistors, damage to semiconductors. That is why this is the test that validates protective devices and their coordination with internal stages.
How to interpret the test
- Equipment that resets but recovers has a logic immunity problem.
- Equipment that stops working with permanent damage indicates that the protection does not limit the voltage or does not divert the current properly.
- A failure that appears after several pulses points to degradation of a protective element.
Safety and current edition
The test uses hazardous voltages and must be carried out by qualified personnel, in line with the applicable safety regulations. This guide only summarizes the scope; the exact waveforms, levels and procedures must be taken from the current edition of the standard and from the product standard that apply in your case.