What is measured
The test evaluates the insulation between the conductor and the metallic shield, which is grounded. This measurement reveals moisture, contamination at terminations or serious damage, but it does not detect incipient localized defects, such as voids or trees, which call for other diagnostics.
Essential steps
- De-energize, isolate and ground both ends of the cable, verifying the absence of voltage and discharging it. A long cable stores considerable charge.
- Disconnect the cable from transformers, switchboards or surge arresters at both ends and keep the terminations separated.
- Measure each phase with the other two and the shield grounded. In this way each conductor is tested against everything else.
- Apply the guard at the terminations if there is surface leakage due to dirt or moisture.
- Record readings at defined times, together with the cable and ambient temperatures.
The effect of length
All the insulation along the cable acts like resistances in parallel. As a result, total resistance decreases as length increases, and a short cable and a long cable of identical quality give different values. To compare cables, values are normalized by length according to the criterion adopted. In addition, a long cable has high capacitance: the charging current takes longer to decay and the reading stabilizes more slowly.
How to interpret the result
Very low values, or values that differ between phases, point to a problem. Acceptable values do not guarantee that the cable will withstand the service voltage; withstand or diagnostic tests are used to confirm this. New cables are compared with the acceptance specification, and existing cables with their history.
When it does not apply
On its own, this test cannot evaluate a cable suspected of electrical treeing or water treeing in the extruded insulation.