How to read the code
The designation uses letters to describe the cooling medium and how it circulates. The IEC scheme uses four letters, in this order:
- The internal cooling fluid: O for mineral oil or another combustible liquid, A for air.
- The type of internal circulation: N natural, F forced and D directed through the windings.
- The external medium: A for air, W for water.
- The external circulation: N natural or F forced.
Examples
| Code | Meaning |
|---|---|
| ONAN | Oil in natural circulation, cooled by natural air |
| ONAF | Natural oil, air forced by fans |
| OFAF | Oil forced by pumps, forced air |
| ODAF | Oil forced and directed through the windings, forced air |
| AN | Dry-type transformer with natural air |
| AF | Dry-type transformer with forced air |
Why it matters
A transformer’s capacity depends on how much heat it can dissipate. Many transformers have several stages: for example, a base capacity with natural cooling and higher ones when fans or pumps come on. The nameplate shows the power for each class. Whoever operates the unit must know which stage is active, because the allowable load changes.
What the engineer sees in practice
- Fan and pump starting is controlled by the temperature indicators. If they do not start, the unit is limited to the capacity of the lower stage.
- A fan or pump failure translates into higher oil temperature and loss of capacity.
- Any overload calculation must take into account the cooling class in operation.
When the same nomenclature does not apply
The IEEE standard uses other designations, such as OA, FA and FOA, with equivalent meaning but written differently. Before comparing nameplates of different origins, verify which scheme each one uses and consult the current edition of the applicable standard.