Definition
The voltage between two windings of a transformer is proportional to the ratio of their numbers of turns. A tap is an intermediate outlet on the winding that lets you choose how many turns to work with. Changing the tap changes the turns ratio and, as a result, the output voltage for a given input voltage.
What they are for
- Compensating for a grid voltage that is consistently above or below the rated value.
- Regulating the secondary voltage as the load and the line drop vary.
- Adapting the same transformer to different installation conditions.
How they are indicated
The nameplate shows the tap changer positions and the voltage for each one, usually on one side of the transformer. They are expressed as a voltage or as a percentage above or below the rated value. The center or nominal position is the one that corresponds to the rated voltage. Each step corresponds to an increment of turns, and the step size is set by the design.
How they are changed
- Off-load: with a tap changer operated while the transformer is de-energized.
- On-load: with a mechanism that changes taps while the unit is in service.
Why they matter in testing
Many measurements depend on the selected tap: turns ratio, winding resistance, impedance and losses vary from one position to another. Every test must therefore record the position, and results must be compared at the same one. A common mistake is to compare values measured on different taps without realizing it.
An example
If a transformer supplied at a voltage below the rated value delivers too little voltage on the secondary, the tap can be moved to a position with fewer turns on the input-voltage side, which raises the output voltage. The direction of the adjustment depends on which winding has the taps; check the nameplate.
Warning: changing taps requires de-energizing and locking out the unit, and must be done by qualified personnel in accordance with applicable regulations.