Why Does Winding Insulation Paper Deteriorate?

Insulation paper deteriorates mainly because of temperature, moisture and oxygen: the cellulose chains break, the paper loses mechanical strength and releases water, acids and gases, and the damage is irreversible.

What it is made of and why it degrades

The solid insulation of windings is cellulose, made up of long chains of glucose molecules. Its mechanical strength depends on the length of those chains. Aging means that the chains break, in other words, that their degree of polymerization falls.

The three main agents

  • Temperature: this is the dominant factor. Chain scission accelerates quickly as temperature rises, which is why the winding hot spot matters more than the average temperature.
  • Moisture: water promotes hydrolysis of the cellulose and accelerates degradation. In addition, water concentrates in the paper rather than in the oil, so the paper can be much wetter than an oil sample suggests.
  • Oxygen: it promotes oxidation and the formation of acids, which in turn catalyze further degradation.

What degradation produces

  1. Water, which adds to what is already there and feeds the process.
  2. Carbon oxides, which appear dissolved in the oil.
  3. Furanic compounds, which dissolve in the oil and serve as an indicator.
  4. Acids, which also attack the oil and the metal parts.

Why it matters

Deteriorated paper retains its dielectric capability longer than its mechanical strength. The risk appears when an external short circuit subjects the winding to large forces: brittle paper cannot withstand them, and the winding deforms or fails. This is why the condition of the paper largely defines the service life of the transformer.

How it is assessed

  • The trend of carbon monoxide and carbon dioxide in dissolved gas analysis.
  • Furanic compounds in the oil.
  • Moisture in the oil and an estimate of the moisture in the paper based on temperature.
  • Direct measurement of the degree of polymerization on paper samples, when they can be accessed.

None of these indicators is conclusive on its own, and interpretation relies on trends and on combining the data.

What can be done

Damage to the paper cannot be reversed. Its progress can be slowed by reducing moisture, preventing oxygen ingress, controlling the operating temperature and limiting overloads.