What causes localized heating in the core?

Localized heating in the core is usually due to abnormal eddy currents: a short circuit between laminations, a double core ground or stray flux in structural parts, and it is detected through thermal gases in the oil.

What makes the core heat up

A core always has hysteresis and eddy current losses, and they are evenly distributed. Localized heating is something else: one region concentrates losses because an unintended current or flux path passes through it.

Main causes

  • Short circuit between laminations: the insulation between laminations is damaged by cutting burrs, impacts, corrosion or contamination. Eddy current circulates between laminations and heats that area.
  • Double core ground: the core must be grounded at a single point. If there are two, a loop forms in which stray flux induces a circulating current that heats the connections and the core.
  • Stray flux in structures: in beams, flanges, bolts and parts of the tank near the windings, stray flux induces currents that heat those parts, especially if the shielding or screens are inadequate.
  • Uninsulated core bolts or metal bridges: these can join laminations or create closed loops.

How it shows up

  • Thermal fault gases in dissolved gas analysis, with a predominance of thermal-fault hydrocarbons and their relationship to the temperature reached.
  • A rise in oil temperature without an equivalent change in load.
  • Abnormal current measured in the core ground conductor.
  • Darkened oil, or oil containing carbon, in advanced cases.

How it is investigated

  1. The dissolved gas trend is reviewed to see whether the pattern is thermal and sustained.
  2. The current in the core ground connection is measured, if accessible.
  3. With the equipment out of service, the insulation resistance from the core to the tank is measured to detect additional grounds.
  4. If the result warrants it, the core is inspected internally.

How to interpret the result

A low-temperature thermal fault can remain stable for years, and a high-temperature one can be destructive. What is decisive is the gas trend, not an isolated reading.

Warning: measurements on energized equipment and internal inspection must be carried out by qualified personnel, in accordance with the applicable regulations.