Why it happens
A transformer tank is a welded structure with many bolted joints: cover, bushings, radiators, valves, inspection openings, indicators and the tap changer mechanism. Each joint relies on a gasket that maintains contact pressure. Over time, that pressure drops and a leak appears.
Frequent causes
- Gasket aging: the elastomer hardens, takes a permanent set or cracks from temperature and exposure to oil.
- Thermal cycling: repeated expansion and contraction loosen bolts and shift joints.
- Vibration: hum and load forces loosen parts and fatigue welds.
- Weld defects or corrosion: porosity, cracks or pitting in the tank or radiators, especially in aggressive environments.
- High internal pressure: overloads, faults or overfilling increase the pressure in the oil.
- Improper assembly: uneven tightening, poorly seated gaskets or damage during interventions.
What is seen in the field
The oil appears as a wet stain or a drip at the joint; on dusty equipment, the oil picks up dirt and marks its path. It is sometimes hard to tell a leak from simple weeping, which is surface wetness without dripping that advances slowly. The oil level in the conservator or on the gauges reveals whether the loss is continuous.
Why it matters
- A low level reduces the insulation and cooling of upper parts.
- A leak can let air and moisture in when the tank goes under negative pressure.
- Spilled oil is an environmental and fire hazard.
How it is located
- Cleaning the area and observing after some time, to see where the oil comes back from.
- Following the trail upward, because oil runs downward.
- Pressure or vacuum tests with the equipment out of service and under procedure, or the use of suitable dyes and detectors.
The correction ranges from retightening to the torque specified by the manufacturer to replacing gaskets or repairing welds. Retightening blindly is not advisable: overtightening crushes the gasket and makes the leak worse.
Warning: work on energized equipment or equipment with hot oil is a matter for qualified personnel, in accordance with the applicable safety regulations.