What is a transformer tap selector with transition resistors?

It is the on-load tap changer system in which a selector chooses the tap with no current flowing and a diverter switch with transition resistors makes the change without interrupting the load or short-circuiting turns.

The problem it solves

Changing taps with the transformer under load demands two things at once: not interrupting the load current, and not short-circuiting the turns between two adjacent taps. If one contact opened before the next one closed, the load would be cut with an arc; if both contacts were closed with nothing in between, a very high current would circulate through the bridged turns. The transition resistor limits that circulating current during the instant when both taps are connected.

How it is organized

  • Selector: chooses the next tap. It operates without carrying the load current, because that branch is already free.
  • Diverter switch: transfers the load from one tap to another. It is the element that actually breaks and makes current, and where the arc forms.
  • Transition resistors: inserted for a very short time during the change. They are sized for brief duty, not continuous duty.
  • Preselector (if present): reverses or disconnects the regulating winding to extend the range with the same taps.

Simplified sequence

  1. The selector prepares the adjacent tap while the load flows through the present one.
  2. The diverter switch connects a resistor into the path; the load is shared between both taps through resistors.
  3. When the movement is complete, the load remains only on the new tap and the resistors are taken out.

The entire process is driven by a stored-energy mechanism, so that once started, the change is completed even if the motor supply fails.

What is seen when it fails

  • Contact wear and coking, with increased resistance in the load path.
  • Transition resistors that are damaged or out of the expected value, visible in the waveform of a dynamic measurement.
  • Diverter compartment oil degraded by arcing, with gases and carbon; this is monitored separately from the main tank oil.

As a mechanical component that interrupts current, it requires maintenance according to the manufacturer and the number of operations.

Warning: work on tap changers and on energized or recently de-energized transformers must be carried out by qualified personnel in accordance with the applicable regulations.