Air-Insulated or Gas-Insulated Switchgear?

Air-insulated switchgear uses air as the insulation between live parts, so it needs more space; gas-insulated switchgear encloses the live parts in sealed compartments with a gas of higher dielectric strength and is much more compact.

The insulating medium changes almost everything

The minimum distance between parts at different voltages depends on the dielectric strength of the medium. Air requires large clearances; a gas such as sulfur hexafluoride, or the alternatives developed to replace it, withstands more voltage over a shorter distance, especially at above-atmospheric pressure. That is why gas-insulated switchgear is smaller.

Air-insulated switchgear

  • Live parts exposed to air inside the enclosure, with metal compartments.
  • Greater footprint and weight.
  • Its dielectric performance depends on the environment: humidity, contamination, dust, altitude and the presence of animals can cause surface discharges.
  • The components are visible and can be inspected and repaired with familiar technology.

Gas-insulated switchgear

  • Busbars, disconnectors and circuit breakers are housed in sealed vessels, protected from the environment.
  • Very compact, useful where space is limited or the environment is aggressive.
  • Requires gas density monitoring: a loss reduces the insulating capability.
  • The gas must be handled with specific procedures and equipment, and sulfur hexafluoride has a strong greenhouse effect, so its handling and disposal are regulated.
  • An internal fault or a major repair may require working on the compartment and recovering the gas.

What the engineer sees in operation

In air-insulated switchgear, deterioration usually shows up as discharge tracks, hot spots at connections or condensation. In gas-insulated switchgear, what is monitored is the density indicator or transmitter, low-pressure alarms and partial discharges measured from the outside, since the live parts cannot be seen.

Selection criteria

Criterion Air Gas
Available space Requires more Very small
Environment Sensitive to contamination Protected by sealing
Maintenance Direct access to parts Little, but specialized
Gas management Not applicable Mandatory

The choice also depends on the availability of spare parts, trained personnel and the applicable environmental regulations. Any work on medium- or high-voltage switchgear must be done by qualified personnel, with the corresponding safety procedures.