How Is the Slip of an Induction Motor Measured?

The slip of an induction motor is measured by comparing its actual speed, measured with a tachometer, with its synchronous speed, which depends on the supply frequency and the number of poles.

What slip is

In an induction motor, the rotor always turns slightly slower than the rotating magnetic field of the stator. That difference is necessary: only if there is relative motion between the field and the rotor are currents induced in the rotor and torque produced. Slip relates that difference to the synchronous speed.

Formulas

  • Synchronous speed in rpm: ns = 120 · f / p, where f is the frequency in hertz and p is the number of poles.
  • Slip: s = (ns − n) / ns, where n is the actual rotor speed. It is usually expressed as a percentage.

How it is measured

  1. Identify the number of poles on the nameplate or deduce it from the stated rated speed, which is slightly below a synchronous speed.
  2. Confirm the supply frequency; on a motor with a drive, use the output frequency.
  3. Measure the speed with an optical tachometer, using a reflective mark on the shaft, with a contact tachometer, or with a stroboscope. The measurement must be made with the motor in steady state.
  4. Calculate the slip with the formula.

An example

A four-pole motor at a frequency of 60 Hz has a synchronous speed of 120 · 60 / 4 = 1800 rpm. If the tachometer reads 1780 rpm, the slip is (1800 − 1780) / 1800, approximately 1.1 percent.

How to interpret the result

Slip increases with load: at no load it is very small, and it grows as the motor is loaded. Comparing it with the nameplate value at full load gives a rough idea of how much load the motor is carrying. This is an estimate, because slip also depends on the supply voltage, the rotor temperature and the design, and the speed differences are small, so tachometer error carries a lot of weight. Abnormally high slip may indicate overload, low voltage or damaged rotor bars.

When it does not apply

In synchronous motors, slip is zero in steady state, so this measurement is meaningless. With a drive, the output frequency should be used in the calculation. Measurements near rotating shafts call for caution and qualified personnel.