What it is and what it is not
IEC 61000-4-30 is a standard on measurement methods. It answers “how is it measured?” and not “what value is acceptable?”. Limits are set by other documents, such as regulations, contracts and compatibility or voltage characteristics standards; IEC 61000-4-30 ensures that the number they are compared with has been obtained in a uniform way.
Which parameters it covers
- Power frequency.
- Magnitude of the supply voltage.
- Flicker.
- Voltage dips, swells and interruptions.
- Voltage unbalance.
- Voltage harmonics and interharmonics.
- Mains signaling voltages, in some cases.
For each parameter it specifies the calculation algorithm, the measurement window and the uncertainty requirements.
Performance classes
The standard defines classes. Class A has the highest accuracy and comparability, for cases such as compliance verification or dispute resolution. Class S is for quality studies and surveys, with less strict requirements. Class B covers older or less demanding instruments, and its role has been shrinking from edition to edition.
Other concepts in the standard
It defines the aggregation of measurements into longer intervals, synchronization with a reference clock, the handling of data during dips or interruptions (flagging) and how to report uncertainty. It also establishes tests to verify that an instrument complies with the class.
How it is used
When choosing an analyzer for a measurement that will be evaluated against a criterion, check that the instrument declares conformity with the required class. When interpreting a report, verify which class and which configuration were used to obtain it.
What to do with this summary
This guide describes only the scope. The requirements for each class and parameter vary between editions; consult the current edition of the standard.