Transformer oil acidity test equipment for sale

We stock machines for measuring transformer oil acidity. For maintenance managers who need to assess the quality of insulating oil.

Transformer oil acidity test

The acidity test measures the acids formed by oxidation of transformer oil under the influence of excessive temperature and oxygen; the reaction is catalyzed by the presence of small metal particles.

What causes acidity in oil

The interaction of O2 and heat with the transformer’s insulating oil forms acids in the oil.

Why it is measured

The test measures the amount of free acids present in the oil, which is crucial for assessing its quality and its ability to insulate and dissipate heat without degrading quickly. A high acidity level can indicate decomposition products, which affect the oil’s performance and service life.

High acidity levels in insulating oil can compromise its dielectric properties, with a decrease in resistivity and an increase in dissipation factor. Ultimately, this impairs the insulating performance of the oil in electrical systems.

How to check oil quality

To assess the insulating property of dielectric oil, a sample is taken and its breakdown voltage is measured. The lower the breakdown voltage, the worse the quality of the oil.

Portable test kit

The acidity of insulating oil can be determined with a simple portable kit. It consists of a polyethylene bottle of rectified spirit (ethyl alcohol), a polyethylene bottle of sodium carbonate solution and a bottle of universal indicator.

KOH titration test

Materials required

  • Transformer oil (sample).
  • Benzyl alcohol or ethanol (95% alcohol or higher).
  • Phenolphthalein indicator.
  • Potassium hydroxide (KOH) solution, generally at a concentration of 0.1 N.
  • Burette or pipette for measuring the volume of the KOH solution.
  • Measuring beaker or flask.
  • Funnel (optional, to make the process easier).
  • Titrator (if you are not using a burette).

Procedure

  1. Sample preparation: take a representative sample of the transformer oil. Filter it if necessary to remove visible particles or impurities.
  2. Sample measurement: measure approximately 50 ml of oil into a measuring beaker or flask.
  3. Adding alcohol: add between 10-15 ml of benzyl alcohol or ethanol to the oil. This helps dissolve the acids present and makes titration easier.
  4. Adding the indicator: add a few drops of phenolphthalein to the oil and alcohol. The indicator changes color (from colorless to pink) when the sample reaches the titration end point.
  5. Titration with KOH: fill a burette with the 0.1 N potassium hydroxide (KOH) solution. Titrate the mixture of oil, alcohol and phenolphthalein with the KOH solution, adding it slowly while stirring the sample. The end point is reached when the solution changes from colorless to a pink color that persists for 30 seconds.

Calculating the acidity

Record the volume of KOH used (in ml).

Interpreting the results

  • Low acid number (below 0.1 mg KOH/g): the oil is in good condition and has low acidity.
  • High acid number: indicates that the oil has begun to decompose, which can be a sign of oil aging or of contamination with water or other acidic compounds.

Precautions

  • Make sure the samples are well mixed and the measurements are accurate.
  • Carry out the process in a well-ventilated area, as some chemicals, such as KOH, can be hazardous.
  • Avoid contaminating the sample with water or foreign substances.

This method allows a simple assessment of transformer oil quality and helps determine whether the oil needs to be replaced or filtered.