Description
This tester determines the dielectric strength value of various insulating oils. It complies with the ASTM D1816 and ASTM D877 standards. It can test six oil samples at the same time, quickly and with accurate results. You can choose from three electrode heads: flat, spherical and hemispherical.
Main technical specifications
- 5.4 LCD screen with Chinese-language menu, temperature and humidity measurement, and clock.
- Operation is simple: it automatically completes boost, hold, stirring, static setting, calculation, data storage and print output.
- If power is cut, it saves the test results automatically.
- It has overvoltage, overcurrent, limit and grounding alarms, for the operator’s personal safety.
- The unique waveform setting function eliminates harmonic wave interference for accurate measurement.
- It uses a CPU and PLC to give the instrument stability and reliability.
- It has a 232 interface, USB port, Bluetooth and wireless transmission for passing data to the computer.
- It is portable, easy to move and easy to use, both indoors and outdoors.
Technical parameters
| Output voltage | 0~80kv (or 0-100kv) |
| THVD | <1% |
| Voltage rise rate | 0.5~5.0kv/s |
| Step-up power | 1.5 kVA |
| Measurement accuracy | ±2% |
| Supply voltage | AC220V±10% |
| Power frequency | 50Hz±2% |
| Power | 200w |
| Applicable temperature | 0~45℃ |
| Applicable humidity | <85% RH |
| Width*height*depth | 770mm*765mm*760mm |
| Net weight | 90 kg |
Dielectric strength, together with the dielectric loss angle tangent, is the main characteristic of the dielectric properties of insulating oil. Interest in studying it arose when mineral oils began to be used as an insulating medium in transformers, more than a hundred years ago.
Physical meaning of the dielectric strength of transformer oils
When the voltage applied to transformer oil is gradually raised, after a time its resistance drops sharply to zero. This means that the oil has lost its dielectric properties and electric current has begun to pass. The voltage at which this happens is called the breakdown voltage.
In practice, the breakdown voltage of a dielectric depends on its thickness: the thicker the layer, the higher the breakdown voltage. Two dielectrics of different origin and the same thickness have different breakdown voltages. That is why a parameter was introduced to characterize a material’s ability to resist breakdown: dielectric strength. In the simplest case, it is the ratio of the breakdown voltage to the thickness of the dielectric. It is measured in V / m, but other units are also used in practice:
- kV / mm
- kV / cm
- V / μm, etc.
In physical terms, dielectric strength is the electric field intensity in a dielectric at which a breakdown occurs at a given location.
What factors affect the dielectric strength of transformer oil?
Fresh, clean transformer oil usually has sufficient dielectric strength for high-voltage applications.
During operation it is affected by high temperature, moisture, atmospheric oxygen and high voltage. The oil becomes contaminated with mechanical particles, water and gas bubbles, and that reduces its dielectric strength. Water is the main enemy of transformer oil dielectric strength.
In switching devices, the dielectric strength of the oil decreases in proportion to the number of operations, because of the increase in carbon content formed by the electric arc.
How to measure the dielectric strength of transformer oil
It is normally determined in the laboratory with special instruments. The classic method uses a high-voltage transformer with a voltage regulator and a measuring cell into which a sample of the oil is poured. The voltage on the secondary winding is gradually increased until a dielectric breakdown occurs, and the breakdown voltage is recorded.
Breakdown voltage values from different samples of the same oil can differ. That is why the mathematical expectation of the breakdown voltage is used in practice, calculated as the average of several successive measurements. Dielectric strength is calculated by dividing the breakdown voltage by the thickness of the dielectric, which here coincides with the distance between the electrodes.