Oil moisture meters for sale or rent
Oil moisture meters are devices that determine the amount of water in industrial oils: transformer, lubricating, turbine, transmission oils and so on. They can also be used for various types of fuel.
This page covers the most important topics on oil moisture:
- how water gets into oil;
- the forms water can take in oil;
- the danger of water in oil;
- how to reliably determine the amount of water in oil;
- the oil moisture meter.
How water gets into industrial oils
The routes of entry fall into two types.
Operating factors
Water forms during operation of oil-filled equipment, or enters through a seal leak. This happens above all under high loads and extreme temperatures, which cause chemical reactions that form water. In transformers, water forms through the aging and oxidation of cellulose. In turbine installations, it forms through condensation of the steam released at high temperatures.
Non-operating factors
Water can enter the oil from the air during transport or while it is stored in containers in a warehouse. For this reason, it is also advisable to use the moisture meter before filling the equipment with oil.
Forms water can take in oil
Water can be present in three forms:
- dissolved water;
- emulsified water;
- free water.
Dissolved water: water associated with active substances that appear as the oil ages, and water adsorbed by mechanical impurities suspended in the oil.
Emulsified water: water globules suspended in the oil. Their size depends on the dew point and the actual temperature of the water-oil emulsion.
Free water: appears as a result of direct entry into the tank.
In new transformer oils with a low aromatic hydrocarbon content, practically all the moisture is dissolved. Dissolved water forms a solution and hardly changes the insulating characteristics; that is, it does not reduce the dielectric strength of the liquid. But when the temperature drops, the water forms as condensate and turns into emulsified water, which increases the dielectric loss of the oil. In aged transformer oils, most of the moisture is bound.
The meter must give the most complete and accurate information regardless of the form the water takes. Moisture content is measured in grams per ton (ppm) or in percent by weight.
Why water is dangerous for oil
Water is a dangerous impurity for any industrial oil. In transformer oil it degrades the insulating properties and can lead to dielectric breakdown. The greatest danger arises when the temperature fluctuates: dissolved moisture impairs the dielectric properties of the insulation and can destroy it.
In addition, water promotes oxidation of industrial oils, changes their viscosity and causes foaming. The strength of the oil film decreases, which accelerates the wear of rubbing parts.
Using diluted engine oil is dangerous because of increased oxidation and corrosion. This makes steel brittle and raises the risk of damage to the internal combustion engine.
If the oil contains additives, more water can cause their loss and the deterioration of the oil’s properties. Water is an insidious impurity: it affects the properties of the oil and also increases the negative influence of other factors.
Moisture content limits in oils
Oils of various origins are used as dielectrics: mineral, silicone and ethers. Their production technology and properties differ, including their tendency to dissolve water.
Hydrocarbon molecules are hydrophobic, so mineral oils have low water solubility, from 30 to 60 ppm (g/t). Silicone oils and esters have a higher saturation limit: 150 to 300 ppm and 300 to 2600 ppm, respectively.
Oil poured into transformers with film or nitrogen protection, sealed bushings and sealed instrument transformers must not exceed 10 ppm (10 g/t) of water. Power transformers without a protective film and leaking bushings must be filled with oil containing no more than 25 ppm of water. Oil with less than 10 ppm is considered dry, but at the time of delivery the moisture can reach 35 ppm, which calls for drying (thermal vacuum or zeolites). The decision to dry is made only when the meter shows that the parameter exceeds the permitted value.
Methods for measuring moisture in oil
The methods for measuring moisture in transformer oil fall into three groups:
- Methods based on water extraction and measurements through chemical reactions. These include Karl Fischer coulometric titration and the calcium hydride (CaH2) method. With calcium hydride, the volume of gases released by the interaction of the hydride with the water in the oil is measured. The Karl Fischer method determines water by automatic coulometric titration: it measures the amount of electricity consumed for the electrolysis of the water in the Karl Fischer reagent.
- Methods based on physical extraction to the equilibrium level and measurements with a gas chromatograph and photoacoustic emission.
- The capacitive sensor method, which indirectly measures the relative saturation of the oil through the change in conductivity of a sensitive film.
Laboratory oil analyses are accurate, but they take a long time, are difficult to perform and require stricter safety measures.
Instruments for working near transformers are bulky and some are outdated. Without timely, accurate information on the condition of the insulating oil, the reliability of high-voltage equipment cannot be ensured. Compact, accurate, fast, reliable and easy-to-use instruments are needed.
How to take transformer oil samples
Measuring moisture correctly takes more than good instruments: the sample must be taken correctly. If the sample is of poor quality or moisture enters the oil during sampling, the results will be false and the wrong decisions will be made about the transformer maintenance program.
For sampling it is advisable to hire a qualified specialist, who should work in good weather (no precipitation, strong wind, etc.). Sampling is done only in dry, clean containers, and each container is filled to at least 95% of its capacity. Immediately afterward it is sealed tightly with a stopper. Samples are kept in a dark place until the moisture test.
Meter characteristics
The meter is designed to determine the mass fraction of moisture in insulating oils, even in small amounts. In addition to the absolute moisture content in ppm, it measures the oil temperature. Accuracy and stability are achieved with a capacitive sensor that is not sensitive to contaminants in the insulating oil.
The device measures water activity and temperature, and from those values it calculates the moisture content (ppm) in mineral transformer oil. Calculation in non-mineral transformer oils and in lubricating oils is possible only after loading the specific parameters of those oils into the device.
Its design is simple and operating it does not require highly qualified personnel. When you press the start button, the moisture and temperature values appear on the indicators. The result, available in ten minutes, lets you move straight on to the next sample.
The protection class allows insulating oil to be tested near transformers in any climate, and the sensor works at ambient temperatures from -40 to +60 degrees Celsius. Reliability is achieved with vandal-resistant metal buttons, metal protection of the sensing element, a stabilized power supply and built-in protection of the electrical equipment.
It can be used independently or as part of mobile laboratories for online oil analysis in the field.
With reliable, timely information on transformer oil moisture, the maintenance program can be corrected in time and serious consequences prevented: accidents and costly repairs.
How to dry industrial oils
There are several ways to remove water from industrial oils: centrifugation, thermal vacuum drying and passing the oil through a zeolite bed.
- Centrifugation is simple, but physically outdated.
- Thermal vacuum drying is more modern: the oil is first heated, and the water vapor and gas that evaporate from its surface are removed by vacuum.
- Zeolite drying stands out for its high efficiency and simplicity. The zeolite sorbent absorbs a lot of water and retains it in its granules. Once saturated, it must be reactivated; the zeolite can then be reused to dry oil.