Why does thermography of a closed panel underestimate the actual temperature?

Thermography of a closed panel underestimates the actual temperature because the camera measures radiation from the outer surface, which is cooler than the internal component; the cover or door attenuates the heat and can block infrared radiation.

What the camera actually measures

A thermal camera detects infrared radiation from the surface it sees and, from that and the configured emissivity, estimates its temperature. It does not see through metal, plastic or ordinary glass, because these materials do not transmit the long-wave infrared that cameras use. With a door closed, the camera reads the temperature of the door and not that of the conductor, terminal or breaker heating up behind it.

Why the door is cooler

  • Temperature drop along the heat path: heat from the component passes to the interior air, to the structure and then to the outer surface, and the temperature falls at each step.
  • Dissipation to the environment: the large surface of the enclosure loses heat by convection and radiation, so its temperature approaches that of the air.
  • Localized component: a small hot spot contributes little power to the whole, so it barely heats the cover.
  • Stratification of the interior air: heat rises, and the hot spot may not be in front of the area inspected.

Factors that worsen the underestimation

  • Emissivity: polished metal surfaces or surfaces painted with glossy finishes emit little and reflect their surroundings; if it is not set correctly, the reading is wrong.
  • Reflections from nearby sources on the surface.
  • Low load: Joule heating grows with the square of the current, so at low load a defective connection may not stand out.

How to manage the limitation

Infrared inspection windows, made of materials that transmit this radiation, allow you to see inside with the door closed, although they attenuate the signal somewhat and require a declared correction factor. Where there is no window, the door reading is interpreted qualitatively and comparatively, for example between similar phases with the same load, and not as an absolute component temperature.

How to interpret the result

A visible difference between phases on the outside almost always indicates a larger difference inside. The absence of external heating does not guarantee good condition. The load at the time of inspection, the emissivity used and the ambient conditions are recorded.

Warning: opening or inspecting energized panels involves electrical and arc hazards. The work must be done by qualified personnel, with the protective equipment and procedures required by the applicable regulations.