The mechanism
The resistance of an electrode is the product of the resistivity of the surrounding ground and a geometric factor. The geometry does not change with the seasons, but the resistivity does. Conduction in soil is mainly ionic, through water with dissolved salts in the pores, and not through the solid particles, which are very poor conductors.
What factors change it
- Moisture: in the dry season the soil loses water and resistivity rises; rain lowers it.
- Temperature: as it falls, ion mobility decreases and resistivity rises. If the water freezes, the increase is marked.
- Dissolved salts: rain can dilute or wash them away, while irrigation and fertilization practices can increase them.
- Compaction and structure: changes in the ground from construction work or erosion alter contact with the electrode.
Which part of the electrode is most affected
The upper layers are more exposed to changes in the weather. An electrode that reaches deep, moist layers or the water table varies much less than a short one. That is why it is recommended that the design take into account the variation in the surface layer and that electrodes penetrate to depths less sensitive to climate.
How to handle the measurements
- Record the date, the condition of the ground (dry, wet, recent rain) and the site temperature with each value.
- Compare measurements made with the same method and the same test electrode arrangement, in similar seasons.
- Distinguish seasonal change from deterioration: a value that rises steadily, year after year, suggests corrosion or loss of connection, not climate.
- Evaluate the design with the reasonable worst case, normally the dry season, and not with the value from a rainy day.
What to do in practice
If the resistance fluctuates so much that it approaches a design limit, improvements are studied, such as longer electrodes, more electrodes, a larger grid or soil treatments. An expected variation within the design margin is not a fault. Before concluding that something has changed, measurement errors are ruled out: poorly placed probes, interference from other metal structures or loose connections in the system.
Warning: work on grounding systems, especially if they are connected to energized installations, must be done by qualified personnel, following the applicable regulations.