How is a power factor test on a transformer interpreted?

A power factor test measures the dielectric losses and capacitance of the insulation between windings and to ground; it is interpreted by comparing with previous values and with other phases and similar units, correcting for temperature, and not from an isolated number.

What the test measures

An AC voltage is applied to an insulation and the resulting current is measured. An ideal insulation is a pure capacitor and the current leads the voltage by 90 degrees. In a real one there is a small resistive component in phase with the voltage, which represents losses. The power factor is the ratio of that loss component to the total current; the dissipation factor is the tangent of the loss angle. For small values the two are practically equal.

Which configurations are measured

Combinations between high-voltage windings, low-voltage windings and ground are tested separately, as are the bushings, with connection modes that isolate the measurement of each part of the insulation. Each result is associated with a specific portion of the equipment.

How it is interpreted

  1. Against the reference: factory values or previous tests of the same transformer, under comparable conditions.
  2. Between phases and between identical units: an isolated deviation draws more attention than a generally high value.
  3. With temperature correction: dielectric losses depend on temperature, so they are referred to a reference temperature using factors that depend on the type of insulation.
  4. With the acceptance guides from standards and manufacturers, which should be consulted in their current edition.

What each change suggests

  • Increase in power factor: moisture, contamination, aging of the insulation or the oil, or a defect in a bushing.
  • Change in capacitance: may indicate movement or deformation of windings, or a fault between layers in a capacitance-graded bushing.

None of these conclusions is definitive on its own: they are checked against oil analysis, insulation resistance and other electrical tests.

How to interpret the result

A rising trend between tests is more informative than a single value. Surface moisture on bushings and in the surroundings can alter the measurement, so weather conditions are noted and the porcelains are cleaned before measuring.

Warning: this test uses high voltage and is performed on de-energized, grounded equipment. It must be carried out by qualified personnel, following the applicable regulations and safety procedures.