Why it matters
Water in the insulating paper (cellulose) reduces dielectric strength, accelerates thermal aging and, at high temperatures, can be released as bubbles under load. Cellulose retains much more water than oil, so the oil is only a partial indicator of the condition of the solid insulation.
Equilibrium between oil and paper
Water is distributed between the oil and the cellulose according to temperature. As the transformer heats up, some of the water moves from the paper into the oil, and as it cools, the water returns. For this reason, a water-in-oil content can only be interpreted together with the oil temperature at the time of sampling and the equilibrium condition, which is reached slowly.
Main methods
- Water content in oil by Karl Fischer titration: measures the water in an oil sample taken carefully to avoid contamination with ambient moisture. The water content of the paper is estimated with published equilibrium curves.
- Insulation dissipation factor or power factor: moisture increases dielectric losses, and the result is interpreted with temperature correction.
- Dielectric response in the frequency or time domain: the response of the insulation is measured over a frequency range and compared with models of the oil-paper system to separate the influence of moisture from that of the oil.
- Paper sample: gives the most direct measurement, but requires access and is impractical on equipment in service.
A caution on interpretation
Estimates based on the oil can be misleading if the transformer is not in thermal equilibrium, if the sample was taken cold with the water still in the paper, or if the oil is heavily aged, because its degradation products modify the solubility of water. Dielectric measurements also depend on the geometry and temperature of the insulation, so they are corrected or performed at a controlled temperature.
How to interpret the result
The result is compared with the transformer’s own history and with interpretation guides published by technical bodies. A rising trend indicates moisture ingress through faulty seals or a faulty breather, or water produced by aging itself. If moisture is high, the corrective action (drying, oil treatment) is decided by weighing cost and risk.
Warning: transformer testing involves electrical risk. It must be performed with the equipment out of service and grounded, by qualified personnel, following the applicable regulations and procedures.