How is current unbalance measured in a three-phase feeder?

Current unbalance in a three-phase feeder is measured by recording the three phase currents simultaneously, and it is expressed as the deviation from the average or, more rigorously, as the ratio between the negative-sequence and positive-sequence components.

What is measured

A balanced three-phase system has three currents of equal magnitude, phase-shifted from one another. Unbalance exists when the magnitudes differ or the angles are not as expected. It is usually due to uneven distribution of single-phase loads among the phases, a three-phase load with a degraded phase, or the loss of a phase.

Two common definitions

  • Deviation from the average: the largest difference between a phase current and the average of the three, divided by that average. It requires only magnitudes and is easy to calculate.
  • Symmetrical components: the system is broken down into positive, negative and zero sequences, and the unbalance is the ratio of the negative sequence to the positive sequence. It requires magnitudes and angles, but it is the definition used in power quality standards.

The two definitions do not give the same number, so always state which one was used.

How it is measured in practice

  1. Install current sensors (clamps or flexible coils) on all three phases, with the correct polarity and the same scale ratio.
  2. Record the three currents simultaneously, and also the voltage if you want to evaluate power or sequences with angle.
  3. Measure the neutral if there is one, because its current reflects the unbalance and the triplen harmonic content.
  4. Record over a period that covers the operating cycles, not a single instantaneous reading, because the load changes.

How to interpret the result

Relative unbalance is higher at light load, so it should be viewed together with the current magnitude. Persistent unbalance with high currents indicates a load-sharing problem, which is corrected by redistributing the loads. A sudden change suggests an equipment failure or the loss of a phase. Current unbalance is usually greater than voltage unbalance, and it is the latter that damages motors by producing negative sequence and heating.

Warning: installing sensors in energized panels involves electrical risk. It must be done by qualified personnel, following the applicable regulations and safety procedures.