24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

How do you determine whether harmonic distortion comes from the load or the network?

To find out whether harmonic distortion comes from the load or the network, compare how harmonic voltage and current vary as the load changes, the direction of harmonic power flow and the background distortion present with the load disconnected.

Why it is not obvious

A nonlinear load injects harmonic current, and that current produces harmonic voltage as it flows through the network impedance. But the network may already carry voltage distorted by other loads or sources, and then linear loads or capacitors absorb harmonic current without being its origin. Measuring distortion at one point is not enough to know who is causing it.

Diagnostic methods

  1. Correlation with the load: if the harmonic current rises and falls with the load and the harmonic voltage follows it, the load is the source. If the harmonic voltage is present with the load off, there is background distortion.
  2. Measurement with the load disconnected: this is the most direct test of background distortion, when it is possible.
  3. Direction of harmonic power: the active harmonic power is calculated for each order. If it flows from the load toward the network, the load is a source; if it flows toward the load, the source is upstream. With resonances the sign can be misleading, and it should not be used on its own.
  4. Harmonic impedance: the ratio between the variations in harmonic voltage and current during load changes gives an estimate of the impedance seen; comparing it with the expected value helps locate the source.
  5. Measurements at several points: at the service entrance and on different internal feeders, to see where the distortion enters.

Common complications

  • Capacitor banks that create resonance and amplify a harmonic order.
  • Several loads with harmonic phases that add up or partially cancel.
  • Variation of the network impedance with the operating configuration.

How to interpret the result

A reliable result comes from agreement among several methods, not from just one. If the background voltage is high, reducing the harmonic current of the load helps but does not eliminate the problem. If the cause is the load, the solution may lie in filters, line reactors or converters with lower harmonic content, and the location of the correction must be chosen with possible resonances in mind.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer