Difference from harmonics
Harmonics are integer multiples of the network frequency and repeat identically in each cycle, because the waveform repeats. Interharmonics appear at intermediate frequencies, between two consecutive harmonics (or below the fundamental), and the waveform no longer repeats exactly from cycle to cycle.
Where they come from
- Frequency converters and cycloconverters: the variable output frequency interacts with the network frequency and generates frequencies that are a combination of both.
- Arc furnaces and welders: the arc is a random process that produces a continuous spectrum.
- Loads with amplitude modulation or cyclic control, and motors whose mechanical load oscillates.
- Telecontrol signals deliberately injected into the network by the electric utility.
What effects they have
- Flicker: an interharmonic close to the fundamental produces beating and modulates the voltage amplitude, with visible flicker.
- Torque pulsations in rotating machines, if they coincide with natural mechanical frequencies.
- Interference with power-line communication systems and telecontrol equipment.
- Additional heating and errors in filters and sensitive equipment.
- Excitation of resonances with capacitors or tuned filters.
How they are measured
The standard IEC 61000-4-7 defines the measurement of harmonics and interharmonics with a window of several cycles that gives fine spectral resolution, and it combines nearby components into groups and subgroups. If the window is not synchronized with the network frequency, the energy of a harmonic spreads into neighboring lines and can be mistaken for interharmonics, so synchronization is a key quality factor for the instrument.
What the engineer sees in practice
In a current spectrum, peaks or bands appear between the harmonics, often varying over time with the load. Diagnosis usually works from effect to cause: you start from a symptom such as flicker or noise in a motor, measure the spectrum and relate it to the operation of nearby converters or processes.