What it is physically
Rapid variations in the RMS voltage modulate the intensity of a lamp, and the eye and brain perceive flicker when the modulation falls within a certain frequency range, with sensitivity peaking at around a few hertz. That is why the annoyance depends not only on the amplitude of the fluctuation but also on how many times per second it occurs.
Where it comes from
The sources are loads whose current varies rapidly and repeatedly: arc furnaces, welders, motors with cyclic loads, compressors and some wind turbines. The fluctuating current produces varying voltage drops across the network impedance, and neighboring loads see them as voltage fluctuation.
The flicker meter
The measurement standard IEC 61000-4-15 describes an instrument that simulates the lamp, eye and brain chain:
- It adapts and normalizes the input voltage.
- It squares the signal to recover the modulation as a low-frequency signal.
- It applies a weighting filter that reproduces human sensitivity as a function of frequency.
- It models the perception and memory of light with a smoothing filter.
- It statistically classifies the instantaneous sensation and calculates the indicator.
What Pst and Plt mean
Pst evaluates a short interval of ten minutes, and a value of one represents the irritability threshold for the reference observer. Plt is obtained by combining several consecutive Pst values, using a cubic mean, to reflect sources that operate for long periods. Acceptance limits are set in the applicable standards and grid codes, and the current edition should be consulted.
How to interpret the result
A high Pst at a connection point indicates that the fluctuations are perceptible, but it does not identify the party responsible: to do that, it is correlated with the load profile and measured at several points. The location of the meter relative to the source and the short-circuit power at the point change the result considerably. A network with higher short-circuit capacity (a stronger network) attenuates the fluctuations produced by the same load.