Why do insulation readings change with ambient humidity?

Insulation readings change with ambient humidity because moisture forms a conductive film on surfaces and can be absorbed by hygroscopic materials, opening leakage paths that reduce the measured resistance without the internal insulation necessarily being damaged.

Two paths for the current

When insulation resistance is measured, the current can travel through the volume of the material or over its surface. Surface current depends heavily on cleanliness and moisture. In a dry environment, a clean surface barely conducts; in a humid environment, a very thin layer of water with dissolved salts is enough to create a leakage path that reduces the measured resistance.

Mechanisms

  • Surface film: adsorbed water dissolves ionic contaminants and makes them conductive. Hygroscopic contamination, such as salt, retains moisture even at moderate relative humidity.
  • Condensation: if the insulation surface is colder than the dew point of the air, liquid water forms. This happens with equipment that cools down at night or is taken from a cold environment to a warm one.
  • Absorption into the volume: porous materials such as paper, wood, varnishes and some polymers absorb water and lose resistivity.
  • Effect on polarization: water modifies dielectric absorption and can alter time-dependent ratios.

What an engineer sees in practice

The same winding measures a lower resistance on a damp morning than on a dry afternoon, and the value rises again as it dries. A low reading that improves when the surface is cleaned and dried indicates a surface problem. A low reading that does not improve indicates moisture in the volume or real deterioration.

How to measure comparably

  1. Record the insulation temperature, relative humidity and weather conditions at each measurement.
  2. Verify that the surface temperature is above the dew point.
  3. Clean and dry the surfaces, such as insulators and terminals.
  4. Use the guard terminal of the instrument to exclude surface current when the aim is to evaluate the volume.
  5. Correct for temperature using the applicable method and compare with previous measurements made under similar conditions.

When deterioration cannot be concluded

A low value on a humid day is not enough to declare insulation defective. The test is repeated under controlled conditions before deciding. Measurements on high-voltage equipment must be made by qualified personnel, de-energizing, grounding and following applicable regulations.