How is the insulation of a current transformer tested in the field?

The insulation of a current transformer is tested in the field with the equipment de-energized and isolated, by measuring the insulation resistance between windings and to ground and, where possible, the capacitance and dissipation factor of the main insulation through the test tap.

What needs to be verified

A high-voltage current transformer has main insulation between the primary winding and ground, and between the primary and the secondary, normally made of oil-impregnated paper or another material, with layers that grade the field. It deteriorates because of moisture, contamination, aging and internal discharges. Field tests aim to detect these changes without dismantling the equipment.

Usual tests

  1. Preliminary inspection: oil leaks, cracks in the porcelain or polymer, oil level, surface contamination and condition of the connections.
  2. Insulation resistance: with a DC voltage instrument, between the primary and ground with the secondary grounded, and between the secondary and ground. It detects significant moisture or contamination.
  3. Capacitance and dissipation factor: measured with a bridge or a power factor test set, normally at an AC voltage below the rated voltage. An increase in losses indicates moisture or aging, and a change in capacitance suggests a short circuit between insulation layers.
  4. Measurement through the tap: many units have a capacitive tap, connected to the last layer, which allows the main insulation and the tap insulation to be measured separately. That tap must be grounded again when the work is finished.
  5. Other tests: ratio and polarity, excitation curve, winding resistance and, on some units, oil analysis.

How to interpret the result

Results are compared with nameplate or commissioning data, with identical units at the same installation and with the historical trend. Temperature affects losses, so it is recorded and corrected using the applicable method. Individual values are not enough: the change between measurements is the most informative.

What to check first

  • That the equipment is de-energized, isolated, grounded and discharged.
  • That the porcelain surface is clean and dry, to avoid measuring surface leakage.
  • That the conductors have been removed from the terminals and the instrument connections, including the guard, are observed.

Safety

The secondary circuit of a current transformer must never be left open with the primary energized: dangerous voltages appear. These tests must be performed by qualified persons following applicable regulations.