How is electric stress distributed between the layers of an insulation system?

When several insulation layers are in series, the AC electric field is distributed inversely to the permittivity of each layer, so the layer with the lowest permittivity carries the highest field. Under direct current, the distribution is determined by the resistivities.

The basic rule

At a boundary between two materials, perpendicular to the field, the electric flux density is conserved. This means that the product of permittivity and field is equal in both layers. If one layer has half the permittivity of the other, it carries twice the electric field. Under AC, and with nearly ideal insulation, each layer behaves like a capacitor in series, and the voltage is distributed inversely to the capacitance of each: the layer with the lowest capacitance takes up the most voltage.

Consequence for voids and gas layers

Air has a lower permittivity than common solid and liquid insulating materials, and its dielectric strength is also lower. A small gas void inside a solid dielectric is subjected to a higher field than the material around it, and withstands less field before discharging. This is the mechanism behind partial discharges in voids.

Direct current: conductivity rules

Under steady-state direct current, a small conduction current flows through all the layers. The field is distributed in proportion to the resistivities: the most resistive layer carries the most field. Because resistivity depends on temperature, moisture and contamination, the distribution changes with conditions. During transients, such as a polarity reversal or energization, the distribution goes from capacitive to resistive with its own time constant.

Practical applications

  • Combined oil and paper insulation: cellulose barriers are placed to divide the oil gaps into smaller sections and improve voltage withstand.
  • Cables with semiconducting and stress-control layers: these reduce the field concentration at irregularities.
  • Terminations with field grading: materials with controlled permittivity or conductivity smooth the field at the ends.

An example

Take insulation with a layer of good dielectric and a layer of air in series: even if the air layer is thin, the field in it is several times the field in the solid. If the field in the air exceeds its dielectric strength, the air discharges even though the solid is far from its limit.

How to interpret it

Field distribution explains why small defects can be critical. Any precise calculation requires the complete geometry, since edges and curvatures raise the local field. Tests in high-voltage installations must be carried out by qualified persons in accordance with the applicable regulations.